Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
160A
Rated voltage
220 - 690V
DIN rail (top hat rail) mounting optional
Yes
Adjustment range undelayed short-circuit release
63 - 630A
Integrated earth fault protection
No
Overload release current setting
25.2 - 63A
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Type of control element
Toggle
Adjustment range short-term delayed short-circuit release
63 - 630A
Degree of protection (IP)
IP20
Motor drive optional
Yes
Complete device with protection unit
Yes
Position of connection for main current circuit
Front side
Number of poles
4
With under voltage release
No
Motor drive integrated
No
Device construction
Built-in device fixed built-in technique
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA068144R1 | XT4N 160 EKIP LS/I IN=63A 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
160A
Rated voltage
220 .. 690V
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
63 .. 630A
Integrated earth fault protection
Overload release current setting
25.2 .. 63A
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Type of control element
Toggle
Adjustment range short-term delayed short-circuit release
63 .. 630A
Degree of protection (IP)
IP20
Motor drive optional
Complete device with protection unit
Position of connection for main current circuit
Front side
Number of poles
4
With under voltage release
Motor drive integrated
Device construction
Built-in device fixed built-in technique
From same serie