Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
160A
Overload release current setting
40.0 - 100A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Adjustment range short-term delayed short-circuit release
100 - 1000A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
With under voltage release
No
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
Yes
With switched-off indicator
No
Position of connection for main current circuit
Front side
Type of control element
Toggle
Motor drive integrated
No
Number of poles
3
Integrated earth fault protection
No
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP20
Rated voltage
220 - 690V
Adjustment range undelayed short-circuit release
100 - 1000A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA067860R1 | XT2H 160 EKIP LS/I IN=100A 3P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
160A
Overload release current setting
40.0 .. 100A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Adjustment range short-term delayed short-circuit release
100 .. 1000A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
With under voltage release
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With switched-off indicator
Position of connection for main current circuit
Front side
Type of control element
Toggle
Motor drive integrated
Number of poles
3
Integrated earth fault protection
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP20
Rated voltage
220 .. 690V
Adjustment range undelayed short-circuit release
100 .. 1000A
From same serie