Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Overload release current setting
640.0 - 1600A
Integrated earth fault protection
No
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 - 19200A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
No
Motor drive optional
Yes
Position of connection for main current circuit
Front side
Number of poles
4
Degree of protection (IP)
IP20
Type of control element
Push button
Motor drive integrated
No
Complete device with protection unit
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA063019R1 | T7S 1600 PR232/P LSI IN=1600A 4P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Overload release current setting
640.0 .. 1600A
Integrated earth fault protection
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 .. 19200A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Motor drive optional
Position of connection for main current circuit
Front side
Number of poles
4
Degree of protection (IP)
IP20
Type of control element
Push button
Motor drive integrated
Complete device with protection unit
From same serie