Aleta.hr
Main Product Image

1SDA062984R1 | T7V 1250 PR332/P LSIRc In=1250A 3p F F M

Code: 1528742

ManufacturerRAZNO
Catalog number1SDA062984R1
Type
EAN code8015644655334

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Overload release current setting

500.0 - 1250A

Rated permanent current Iu

1250A

Adjustment range short-term delayed short-circuit release

750.0 - 12500A

Rated voltage

690 - 690V

Adjustment range undelayed short-circuit release

1875.0 - 18750A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

No

With switched-off indicator

No

Suitable for DIN rail (top hat rail) mounting

No

With under voltage release

No

Number of poles

3

Position of connection for main current circuit

Front side

Complete device with protection unit

Yes

Motor drive integrated

No

Device construction

Built-in device fixed built-in technique

Type of control element

Push button

Integrated earth fault protection

No

Degree of protection (IP)

IP20

Motor drive optional

Yes


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA062984R1 | T7V 1250 PR332/P LSIRc In=1250A 3p F F M

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Overload release current setting

500.0 .. 1250A

Rated permanent current Iu

1250A

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Rated voltage

690 .. 690V

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

With switched-off indicator

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Number of poles

3

Position of connection for main current circuit

Front side

Complete device with protection unit

Motor drive integrated

Device construction

Built-in device fixed built-in technique

Type of control element

Push button

Integrated earth fault protection

Degree of protection (IP)

IP20

Motor drive optional