Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
500.0 - 1250A
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Rated permanent current Iu
1250A
Number of auxiliary contacts as change-over contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
With switched-off indicator
No
Motor drive integrated
No
Type of control element
Push button
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Integrated earth fault protection
No
Number of poles
3
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP20
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
No
Motor drive optional
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA062981R1 | T7V 1250 PR332/P LI In=1250A 3p

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
500.0 .. 1250A
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Rated permanent current Iu
1250A
Number of auxiliary contacts as change-over contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
With switched-off indicator
Motor drive integrated
Type of control element
Push button
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Integrated earth fault protection
Number of poles
3
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP20
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
From same serie