

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Rated permanent current Iu
1000A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
400.0 - 1000A
Type of control element
Push button
Adjustment range undelayed short-circuit release
1500.0 - 12000A
Motor drive optional
Yes
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of poles
4
Number of auxiliary contacts as change-over contact
0
Motor drive integrated
No
With switched-off indicator
No
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA062859R1 | T7V 1000 PR232/P LSI IN=1000A 4P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Rated permanent current Iu
1000A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
400.0 .. 1000A
Type of control element
Push button
Adjustment range undelayed short-circuit release
1500.0 .. 12000A
Motor drive optional
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of poles
4
Number of auxiliary contacts as change-over contact
0
Motor drive integrated
With switched-off indicator
Complete device with protection unit
Degree of protection (IP)
IP20
From same serie
We use cookies to enhance your experience.