Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
400.0 - 1000A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Rated permanent current Iu
1000A
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
No
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
0
Type of control element
Toggle
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
Yes
Number of poles
4
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
No
Motor drive optional
No
Degree of protection (IP)
IP20
From same serie
1SDA062783R1 | T7H 1000 PR332/P LSIG IN=1000A 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
400.0 .. 1000A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Rated permanent current Iu
1000A
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
DIN rail (top hat rail) mounting optional
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
0
Type of control element
Toggle
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
Number of poles
4
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP20