

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
No
Rated permanent current Iu
1000A
Adjustment range undelayed short-circuit release
1000 - 10000A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
1000 - 10000A
Overload release current setting
400.0 - 1000A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Front side
With switched-off indicator
No
DIN rail (top hat rail) mounting optional
No
Motor drive optional
No
Degree of protection (IP)
IP20
Complete device with protection unit
Yes
Motor drive integrated
No
Number of auxiliary contacts as normally open contact
0
Type of control element
Toggle
Number of poles
4
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA062777R1 | T7H 1000 PR231/P I IN=1000A 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Rated permanent current Iu
1000A
Adjustment range undelayed short-circuit release
1000 .. 10000A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
1000 .. 10000A
Overload release current setting
400.0 .. 1000A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Front side
With switched-off indicator
DIN rail (top hat rail) mounting optional
Motor drive optional
Degree of protection (IP)
IP20
Complete device with protection unit
Motor drive integrated
Number of auxiliary contacts as normally open contact
0
Type of control element
Toggle
Number of poles
4
From same serie
We use cookies to enhance your experience.