Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1000A
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Yes
Number of auxiliary contacts as change-over contact
0
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
No
Number of poles
4
Motor drive optional
No
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
690 - 690V
Complete device with protection unit
Yes
With switched-off indicator
No
Overload release current setting
400.0 - 1000A
Position of connection for main current circuit
Front side
Motor drive integrated
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA062751R1 | T7S 1000 PR332/P LSIG IN=1000A 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1000A
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
0
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
Number of poles
4
Motor drive optional
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
690 .. 690V
Complete device with protection unit
With switched-off indicator
Overload release current setting
400.0 .. 1000A
Position of connection for main current circuit
Front side
Motor drive integrated