Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Overload release current setting
320.0 - 800A
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
800A
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive integrated
No
Degree of protection (IP)
IP20
With switched-off indicator
No
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Complete device with protection unit
Yes
Motor drive optional
No
From same serie
1SDA062684R1 | T7L 800 PR331/P LSIG IN=800A 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Overload release current setting
320.0 .. 800A
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
800A
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive integrated
Degree of protection (IP)
IP20
With switched-off indicator
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Complete device with protection unit
Motor drive optional
From same serie