1SDA061991R1 | T7S 800 PR331/P LSIG IN=800A 4P

Code: 1527758

ManufacturerRAZNO
Catalog number1SDA061991R1
Type
EAN code8015644645373

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

800A

Adjustment range short-term delayed short-circuit release

480.0 - 8000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Adjustment range undelayed short-circuit release

1200.0 - 12000A

Integrated earth fault protection

Yes

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

No

Suitable for DIN rail (top hat rail) mounting

No

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

0

Position of connection for main current circuit

Front side

Type of control element

Push button

With switched-off indicator

No

Rated voltage

690 - 690V

Motor drive optional

Yes

Complete device with protection unit

Yes

Overload release current setting

320.0 - 800A

Device construction

Built-in device fixed built-in technique

Degree of protection (IP)

IP20

Number of poles

4

Motor drive integrated

No


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA061991R1 | T7S 800 PR331/P LSIG IN=800A 4P

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

800A

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Integrated earth fault protection

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

0

Position of connection for main current circuit

Front side

Type of control element

Push button

With switched-off indicator

Rated voltage

690 .. 690V

Motor drive optional

Complete device with protection unit

Overload release current setting

320.0 .. 800A

Device construction

Built-in device fixed built-in technique

Degree of protection (IP)

IP20

Number of poles

4

Motor drive integrated