Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
1000A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
600.0 - 7600A
Integrated earth fault protection
No
Overload release current setting
400.0 - 1000A
With under voltage release
No
Adjustment range undelayed short-circuit release
1500.0 - 10500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
With switched-off indicator
No
Type of control element
Toggle
Number of poles
4
Complete device with protection unit
Yes
Motor drive integrated
No
Degree of protection (IP)
IP20
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Device construction
Built-in device fixed built-in technique
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA060568R1 | T6H 1000 PR222DS/P-LSI IN=1000 4

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
1000A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
600.0 .. 7600A
Integrated earth fault protection
Overload release current setting
400.0 .. 1000A
With under voltage release
Adjustment range undelayed short-circuit release
1500.0 .. 10500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
With switched-off indicator
Type of control element
Toggle
Number of poles
4
Complete device with protection unit
Motor drive integrated
Degree of protection (IP)
IP20
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Motor drive optional