Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1000 - 10000A
Adjustment range short-term delayed short-circuit release
1000 - 10000A
Rated voltage
690 - 690V
Integrated earth fault protection
No
Overload release current setting
320.0 - 800A
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Complete device with protection unit
Yes
Number of poles
4
Motor drive optional
Yes
With switched-off indicator
No
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
0
Degree of protection (IP)
IP20
Motor drive integrated
No
From same serie
1SDA060283R1 | T6S 800 PR221DS-LS/I IN=800 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1000 .. 10000A
Adjustment range short-term delayed short-circuit release
1000 .. 10000A
Rated voltage
690 .. 690V
Integrated earth fault protection
Overload release current setting
320.0 .. 800A
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Complete device with protection unit
Number of poles
4
Motor drive optional
With switched-off indicator
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
0
Degree of protection (IP)
IP20
Motor drive integrated
From same serie