- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
630A
Adjustment range short-term delayed short-circuit release
1000 - 10000A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
1000 - 10000A
Rated voltage
690 - 690V
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
DIN rail (top hat rail) mounting optional
No
Overload release current setting
252.0 - 630A
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
No
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
No
Type of control element
Toggle
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Complete device with protection unit
Yes
Motor drive optional
Yes
From same serie
1SDA060242R1 | T6S 630 PR221DS-I IN=630 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
630A
Adjustment range short-term delayed short-circuit release
1000 .. 10000A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
1000 .. 10000A
Rated voltage
690 .. 690V
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
DIN rail (top hat rail) mounting optional
Overload release current setting
252.0 .. 630A
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
Type of control element
Toggle
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Complete device with protection unit
Motor drive optional