Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Overload release current setting
252.0 - 630A
Rated permanent current Iu
630A
Adjustment range short-term delayed short-circuit release
378.0 - 6300A
Adjustment range undelayed short-circuit release
945.0 - 7560A
Complete device with protection unit
Yes
With switched-off indicator
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Number of poles
3
Motor drive optional
Yes
DIN rail (top hat rail) mounting optional
No
Type of control element
Toggle
With under voltage release
No
Integrated earth fault protection
Yes
Rated voltage
690 - 690V
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP20
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
No
From same serie
1SDA060229R1 | T6N 630 PR222DS/P-LSIG IN=630 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Overload release current setting
252.0 .. 630A
Rated permanent current Iu
630A
Adjustment range short-term delayed short-circuit release
378.0 .. 6300A
Adjustment range undelayed short-circuit release
945.0 .. 7560A
Complete device with protection unit
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Number of poles
3
Motor drive optional
DIN rail (top hat rail) mounting optional
Type of control element
Toggle
With under voltage release
Integrated earth fault protection
Rated voltage
690 .. 690V
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP20
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated