Technical specifications
With under voltage release
No
Rated permanent current Iu
320A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Integrated earth fault protection
No
Adjustment range undelayed short-circuit release
480.0 - 3840A
Adjustment range short-term delayed short-circuit release
192.0 - 3200A
Overload release current setting
128.0 - 320A
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Number of poles
4
With switched-off indicator
No
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Motor drive integrated
No
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Motor drive optional
Yes
From same serie
1SDA059496R1 | T4N 320 PR223DS IN=320 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With under voltage release
Rated permanent current Iu
320A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Integrated earth fault protection
Adjustment range undelayed short-circuit release
480.0 .. 3840A
Adjustment range short-term delayed short-circuit release
192.0 .. 3200A
Overload release current setting
128.0 .. 320A
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Number of poles
4
With switched-off indicator
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Motor drive integrated
Complete device with protection unit
Degree of protection (IP)
IP20