Aleta.hr
Main Product Image

1SDA054539R1 | T5V400 PR221DS-LS/I IN=400 3P F

Code: 1526620

ManufacturerRAZNO
Catalog number1SDA054539R1
Type
EAN code8015644556402

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

-kA

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Type of electrical connection of main circuit

Bolt connection

Number of poles

3

Device construction

Built-in device fixed built-in technique

Overload release current setting

160.0 - 400A

Position of connection for main current circuit

Front side

Adjustment range short-term delayed short-circuit release

400 - 4000A

Integrated earth fault protection

No

DIN rail (top hat rail) mounting optional

No

Suitable for DIN rail (top hat rail) mounting

No

With switched-off indicator

No

Adjustment range undelayed short-circuit release

400 - 4000A

Degree of protection (IP)

IP20

Motor drive integrated

No

Motor drive optional

Yes

Complete device with protection unit

Yes

With under voltage release

No

Type of control element

Toggle

Rated permanent current Iu

400A

Rated voltage

1150 - 1150V


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA054539R1 | T5V400 PR221DS-LS/I IN=400 3P F

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

-kA

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Type of electrical connection of main circuit

Bolt connection

Number of poles

3

Device construction

Built-in device fixed built-in technique

Overload release current setting

160.0 .. 400A

Position of connection for main current circuit

Front side

Adjustment range short-term delayed short-circuit release

400 .. 4000A

Integrated earth fault protection

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

With switched-off indicator

Adjustment range undelayed short-circuit release

400 .. 4000A

Degree of protection (IP)

IP20

Motor drive integrated

Motor drive optional

Complete device with protection unit

With under voltage release

Type of control element

Toggle

Rated permanent current Iu

400A

Rated voltage

1150 .. 1150V