Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
200kA
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
945.0 - 5985A
Overload release current setting
252.0 - 630A
DIN rail (top hat rail) mounting optional
No
Number of poles
4
Type of control element
Toggle
Integrated earth fault protection
No
Motor drive optional
Yes
Rated permanent current Iu
630A
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Yes
Adjustment range short-term delayed short-circuit release
378.0 - 6300A
With switched-off indicator
No
Motor drive integrated
No
With under voltage release
No
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA054434R1 | T5V 630 PR222DS/P-LSI IN=630 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
200kA
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
945.0 .. 5985A
Overload release current setting
252.0 .. 630A
DIN rail (top hat rail) mounting optional
Number of poles
4
Type of control element
Toggle
Integrated earth fault protection
Motor drive optional
Rated permanent current Iu
630A
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Adjustment range short-term delayed short-circuit release
378.0 .. 6300A
With switched-off indicator
Motor drive integrated
With under voltage release
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
From same serie