Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
400A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
No
DIN rail (top hat rail) mounting optional
No
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Overload release current setting
128.0 - 320A
With switched-off indicator
No
Motor drive optional
Yes
Type of control element
Toggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
200kA
Complete device with protection unit
Yes
Adjustment range short-term delayed short-circuit release
320 - 3200A
Degree of protection (IP)
IP20
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
320 - 3200A
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA054382R1 | T5V 400 PR221DS-I IN=320 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
400A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Overload release current setting
128.0 .. 320A
With switched-off indicator
Motor drive optional
Type of control element
Toggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
200kA
Complete device with protection unit
Adjustment range short-term delayed short-circuit release
320 .. 3200A
Degree of protection (IP)
IP20
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
320 .. 3200A
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
From same serie