Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
160.0 - 400A
Rated permanent current Iu
400A
Rated voltage
690 - 690V
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Adjustment range short-term delayed short-circuit release
240.0 - 4000A
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Type of control element
Toggle
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
No
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Front side
Adjustment range undelayed short-circuit release
600.0 - 4800A
Number of poles
3
Degree of protection (IP)
IP20
DIN rail (top hat rail) mounting optional
No
Complete device with protection unit
Yes
Motor drive optional
Yes
Motor drive integrated
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA054323R1 | T5N 400 PR222DS/P-LSIG IN=400 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
160.0 .. 400A
Rated permanent current Iu
400A
Rated voltage
690 .. 690V
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Adjustment range short-term delayed short-circuit release
240.0 .. 4000A
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Type of control element
Toggle
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Front side
Adjustment range undelayed short-circuit release
600.0 .. 4800A
Number of poles
3
Degree of protection (IP)
IP20
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Motor drive optional
Motor drive integrated
From same serie