Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Integrated earth fault protection
No
Rated permanent current Iu
400A
Overload release current setting
128.0 - 320A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
DIN rail (top hat rail) mounting optional
No
Type of control element
Toggle
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
320 - 3200A
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Yes
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Yes
Motor drive integrated
No
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP20
Number of poles
3
Position of connection for main current circuit
Front side
With switched-off indicator
No
Adjustment range undelayed short-circuit release
320 - 3200A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA054316R1 | T5N 400 PR221DS-LS IN=320 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Integrated earth fault protection
Rated permanent current Iu
400A
Overload release current setting
128.0 .. 320A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
DIN rail (top hat rail) mounting optional
Type of control element
Toggle
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
320 .. 3200A
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Motor drive integrated
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP20
Number of poles
3
Position of connection for main current circuit
Front side
With switched-off indicator
Adjustment range undelayed short-circuit release
320 .. 3200A