Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With under voltage release
No
DIN rail (top hat rail) mounting optional
No
Rated permanent current Iu
250A
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Integrated earth fault protection
No
Motor drive optional
Yes
Number of poles
3
Adjustment range undelayed short-circuit release
240.0 - 1920A
Number of auxiliary contacts as normally open contact
0
Type of control element
Toggle
Motor drive integrated
No
Overload release current setting
64.0 - 160A
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
No
Number of auxiliary contacts as change-over contact
0
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Yes
Adjustment range short-term delayed short-circuit release
96.0 - 1600A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA054076R1 | T4L 250 PR222DS/P-LSI IN=160 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With under voltage release
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
250A
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Integrated earth fault protection
Motor drive optional
Number of poles
3
Adjustment range undelayed short-circuit release
240.0 .. 1920A
Number of auxiliary contacts as normally open contact
0
Type of control element
Toggle
Motor drive integrated
Overload release current setting
64.0 .. 160A
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Number of auxiliary contacts as change-over contact
0
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Adjustment range short-term delayed short-circuit release
96.0 .. 1600A
From same serie