Details
- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
100A
Overload release current setting
80 - 100A
Switch off technique
Thermomagnetic
Phase failure sensitive
Yes
Rated operation power at AC-3, 400 V
55kW
Rated operation power at AC-3, 230 V
30kW
With thermal protection
Yes
Adjustment range undelayed short-circuit release
800 - 1250A
Rated operating voltage
440 - 440V
Type of electrical connection of main circuit
Other
Type of control element
Rocker lever
With integrated auxiliary switch
No
Device construction
Built-in device plug-in technique
Height
201mm
Rated short-circuit breaking capacity lcu at 400 V, AC
18.5kA
Width
95mm
Number of poles
3
With integrated under voltage release
No
Degree of protection (IP)
IP20
Depth
90mm
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
Related products
From same serie
NZMB1-M100-SVE
Details
- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
100A
Overload release current setting
80 .. 100A
Switch off technique
Thermomagnetic
Phase failure sensitive
Rated operation power at AC-3, 400 V
55kW
Rated operation power at AC-3, 230 V
30kW
With thermal protection
Adjustment range undelayed short-circuit release
800 .. 1250A
Rated operating voltage
440 .. 440V
Type of electrical connection of main circuit
Other
Type of control element
Rocker lever
With integrated auxiliary switch
Device construction
Built-in device plug-in technique
Height
201mm
Rated short-circuit breaking capacity lcu at 400 V, AC
18.5kA
Width
95mm
Number of poles
3
With integrated under voltage release
Degree of protection (IP)
IP20
Depth
90mm
From same serie