

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
250A
Overload release current setting
125 - 250A
Adjustment range undelayed short-circuit release
500 - 2750A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Screw connection
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
0 - 0A
With switched-off indicator
No
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
With integrated under voltage release
No
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Yes
Integrated earth fault protection
No
Complete device with protection unit
Yes
Motor drive integrated
No
Degree of protection (IP)
IP20
Type of control element
Rocker lever
Position of connection for main current circuit
Front side
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
Related products
From same serie
NZMN3-AE250-AVE

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
250A
Overload release current setting
125 .. 250A
Adjustment range undelayed short-circuit release
500 .. 2750A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Screw connection
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
0 .. 0A
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
With integrated under voltage release
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Integrated earth fault protection
Complete device with protection unit
Motor drive integrated
Degree of protection (IP)
IP20
Type of control element
Rocker lever
Position of connection for main current circuit
Front side
Number of poles
3
Number of auxiliary contacts as normally open contact
0
From same serie
Related products
We use cookies to enhance your experience.