Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Overload release current setting
200 - 400A
Device construction
Built-in device slide-in technique (withdrawable)
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
No
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
No
DIN rail (top hat rail) mounting optional
No
Complete device with protection unit
Yes
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP20
Motor drive integrated
No
Motor drive optional
Yes
Type of control element
Rocker lever
Position of connection for main current circuit
Front side
Number of poles
4
Rated permanent current Iu
400A
Type of electrical connection of main circuit
Screw connection
Adjustment range short-term delayed short-circuit release
400 - 4000A
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
800 - 4400A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
Related products
From same serie
NZMN3-4-VE400-AVE

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Overload release current setting
200 .. 400A
Device construction
Built-in device slide-in technique (withdrawable)
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP20
Motor drive integrated
Motor drive optional
Type of control element
Rocker lever
Position of connection for main current circuit
Front side
Number of poles
4
Rated permanent current Iu
400A
Type of electrical connection of main circuit
Screw connection
Adjustment range short-term delayed short-circuit release
400 .. 4000A
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
800 .. 4400A