Details
- Low-voltage industrial components
- Switch disconnector (low voltage)
- 1 KOM
- EATON
Technical specifications
Max. rated operation voltage Ue AC
690V
Rated permanent current at AC-23, 400 V
63A
Version as main switch
Yes
Version as maintenance-/service switch
Yes
Rated operating voltage
690 - 690V
Version as emergency stop installation
No
Version as reversing switch
No
Switching power at 400 V
30kW
Rated operation power at AC-3, 400 V
22kW
Rated permanent current at AC-21, 400 V
63A
Version as safety switch
No
Number of switches
1
Number of auxiliary contacts as normally closed contact
0
Number of poles
2
Rated short-time withstand current lcw
1.3kA
Conditioned rated short-circuit current Iq
2kA
Rated permanent current Iu
63A
Number of auxiliary contacts as normally open contact
0
Rated operation power at AC-23, 400 V
30kW
Suitable for front mounting centre
No
Suitable for intermediate mounting
Yes
Voltage release optional
No
Device construction
Built-in device fixed built-in technique
Colour control element
Black
Suitable for distribution board installation
No
Motor drive optional
No
Motor drive integrated
No
Type of control element
Door coupling rotary drive
Degree of protection (IP), front side
IP65
Suitable for front mounting 4-hole
No
Height
88mm
Suitable for floor mounting
Yes
Interlockable
Yes
Degree of protection (NEMA)
12
Type of electrical connection of main circuit
Screw connection
Depth
138mm
With pre-assembled cabling
No
Number of auxiliary contacts as change-over contact
0
Width
88mm
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
T5B-1-102/V/SVB-SW

Details
- Low-voltage industrial components
- Switch disconnector (low voltage)
- 1 KOM
- EATON
Technical specifications
Max. rated operation voltage Ue AC
690V
Rated permanent current at AC-23, 400 V
63A
Version as main switch
Version as maintenance-/service switch
Rated operating voltage
690 .. 690V
Version as emergency stop installation
Version as reversing switch
Switching power at 400 V
30kW
Rated operation power at AC-3, 400 V
22kW
Rated permanent current at AC-21, 400 V
63A
Version as safety switch
Number of switches
1
Number of auxiliary contacts as normally closed contact
0
Number of poles
2
Rated short-time withstand current lcw
1.3kA
Conditioned rated short-circuit current Iq
2kA
Rated permanent current Iu
63A
Number of auxiliary contacts as normally open contact
0
Rated operation power at AC-23, 400 V
30kW
Suitable for front mounting centre
Suitable for intermediate mounting
Voltage release optional
Device construction
Built-in device fixed built-in technique
Colour control element
Black
Suitable for distribution board installation
Motor drive optional
Motor drive integrated
Type of control element
Door coupling rotary drive
Degree of protection (IP), front side
IP65
Suitable for front mounting 4-hole
Height
88mm
Suitable for floor mounting
Interlockable
Degree of protection (NEMA)
12
Type of electrical connection of main circuit
Screw connection
Depth
138mm
With pre-assembled cabling
Number of auxiliary contacts as change-over contact
0
Width
88mm
From same serie