Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
630A
Type of electrical connection of main circuit
Screw connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
With switched-off indicator
No
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Front side
With integrated under voltage release
No
Number of poles
4
Adjustment range short-term delayed short-circuit release
472 - 4410A
Number of auxiliary contacts as change-over contact
0
Complete device with protection unit
Yes
Adjustment range undelayed short-circuit release
1260 - 5040A
Degree of protection (IP)
IP20
Motor drive optional
Yes
Motor drive integrated
No
Type of control element
Rocker lever
Overload release current setting
315 - 630A
Integrated earth fault protection
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
Related products
From same serie
NZMN3-4-VE630/400

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
630A
Type of electrical connection of main circuit
Screw connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
With switched-off indicator
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Front side
With integrated under voltage release
Number of poles
4
Adjustment range short-term delayed short-circuit release
472 .. 4410A
Number of auxiliary contacts as change-over contact
0
Complete device with protection unit
Adjustment range undelayed short-circuit release
1260 .. 5040A
Degree of protection (IP)
IP20
Motor drive optional
Motor drive integrated
Type of control element
Rocker lever
Overload release current setting
315 .. 630A
Integrated earth fault protection
From same serie
Related products