Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Integrated earth fault protection
No
Overload release current setting
125 - 250A
Type of electrical connection of main circuit
Screw connection
Rated permanent current Iu
250A
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
With switched-off indicator
No
With integrated under voltage release
No
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Front side
Number of poles
3
Type of control element
Rocker lever
Adjustment range undelayed short-circuit release
500 - 2750A
Rated voltage
690 - 690V
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP20
Adjustment range short-term delayed short-circuit release
250 - 2500A
Complete device with protection unit
Yes
Motor drive optional
Yes
Zagreb:
0 pcs
Zadar:
0 pcs
NZMH3-VE250
Code
1028371
Catalog number
259134
Type
Power circuit-breaker for trafo/generator/installation protection
Manufacturer
Eaton (Moeller)Serie
-
1.738,57 €
Total stock:
0 PCS
150kA
125 .. 250A
Screw connection
250A
0
0
Built-in device fixed built-in technique
Front side
3
Rocker lever
500 .. 2750A
690 .. 690V
0
IP20
250 .. 2500A