Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Rated permanent current Iu
630A
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
Position of connection for main current circuit
Connection at separate chassis part
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
252.0 - 630A
Adjustment range undelayed short-circuit release
945.0 - 9450A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Integrated earth fault protection
No
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
No
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA072054R1 | E1.2B 630 EKIP TOUCH LI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Rated permanent current Iu
630A
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Position of connection for main current circuit
Connection at separate chassis part
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
252.0 .. 630A
Adjustment range undelayed short-circuit release
945.0 .. 9450A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Integrated earth fault protection
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
Motor drive optional
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button