

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2000.0 - 5000A
Integrated earth fault protection
No
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Rated permanent current Iu
5000A
Adjustment range short-term delayed short-circuit release
3000.0 - 50000A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Number of poles
4
Complete device with protection unit
Yes
With switched-off indicator
Yes
Motor drive integrated
No
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
4
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA071905R1 | E6.2V 5000 EKIP TOUCH LSI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2000.0 .. 5000A
Integrated earth fault protection
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Rated permanent current Iu
5000A
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Number of poles
4
Complete device with protection unit
With switched-off indicator
Motor drive integrated
Motor drive optional
Number of auxiliary contacts as change-over contact
4
From same serie
We use cookies to enhance your experience.