Aleta.hr
Main Product Image

2CSR275189R1404 | DS201 M C40 A30 110V

Code: 1992783

ManufacturerABB
Catalog number2CSR275189R1404
EAN code8012542594215
Order only
Zagreb0 pcs
Zadar0 pcs

Sign in or create an account for lower prices and other benefits


WSP*
115,94 €
Neto115,94
RP144,93
pcs

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Suitable for flush-mounted installation

No

Number of poles (total)

2

Number of protected poles

1

Rated voltage

240V

Rated insulation voltage Ui

500V

Rated impulse withstand voltage Uimp

4kV

Rated current

40A

Rated fault current

0.03A

Leakage current type

A

Current limiting class

3

Power loss

9.1W

Rated short-circuit breaking capacity according to EN 61009

10kA

Rated short-circuit breaking capacity according to IEC 60947-2

15kA

Rated short-circuit breaking capacity Icn according to EN 61009-1

10kA

Disconnection characteristic

Undelayed

Surge current capacity

-kA

Voltage type

AC

Frequency

50/60 Hz

Release characteristic

C

Concurrently switching neutral conductor

Yes

With interlocking device

No

Over voltage category

3

Pollution degree

2

Ambient temperature during operating

-25 - 55°C

Width in number of modular spacings

2

Built-in depth

69mm

Flush-mounted installation

No

Anti-nuisance tripping version

No

Degree of protection (IP)

IP20

Connectable conductor cross section solid-core

- - -mm²

Connectable conductor cross section multi-wired

0.75 - 16mm²


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

2CSR275189R1404 | DS201 M C40 A30 110V

Main Product Image

Code

1992783

Catalog number

DS201MC40A30110V

Type

Earth leakage circuit breaker

Manufacturer

ABB

Serie

-

Neto WSP:

115,94

RP:144,93
* Minimum quantity1

Total stock:

0 PCS

Zadar0 PCS
Zagreb0 PCS

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Suitable for flush-mounted installation

Number of poles (total)

2

Number of protected poles

1

Rated voltage

240V

Rated insulation voltage Ui

500V

Rated impulse withstand voltage Uimp

4kV

Rated current

40A

Rated fault current

0.03A

Leakage current type

A

Current limiting class

3

Power loss

9.1W

Rated short-circuit breaking capacity according to EN 61009

10kA

Rated short-circuit breaking capacity according to IEC 60947-2

15kA

Rated short-circuit breaking capacity Icn according to EN 61009-1

10kA

Disconnection characteristic

Undelayed

Surge current capacity

-kA

Voltage type

AC

Frequency

50/60 Hz

Release characteristic

C

Concurrently switching neutral conductor

With interlocking device

Over voltage category

3

Pollution degree

2

Ambient temperature during operating

-25 .. 55°C

Width in number of modular spacings

2

Built-in depth

69mm

Flush-mounted installation

Anti-nuisance tripping version

Degree of protection (IP)

IP20

Connectable conductor cross section solid-core

- .. -mm²

Connectable conductor cross section multi-wired

0.75 .. 16mm²

From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

We use cookies to enhance your experience.