Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
6300A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
3780.0 - 63000A
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Number of poles
4
With under voltage release
No
Complete device with protection unit
Yes
Type of control element
Push button
Overload release current setting
2520.0 - 6300A
Motor drive integrated
No
Degree of protection (IP)
IP30
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Motor drive optional
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA073365R1 | E6.2H/F 6300 EKIP TOUCH LSI 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
6300A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
3780.0 .. 63000A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Number of poles
4
With under voltage release
Complete device with protection unit
Type of control element
Push button
Overload release current setting
2520.0 .. 6300A
Motor drive integrated
Degree of protection (IP)
IP30
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Motor drive optional
From same serie